SPECIFICATIONS
- Height Maximum 2367 mm93.2 in
- Length Maximum 5919 mm232.9 in
- Width Maximum 2286 mm90 in
- Minimum Rating 1600 kVA
- Maximum Rating 2000 kVA
- Voltage 220 to 13800
- Frequency 50 Hz
- Speed 1500 rpm
- Emissions Fuel Strategy Low Fuel Consumption
- Engine Model 3516 TA, V-16, 4-Stroke Water-Cooled Diesel
- Compression Ratio 13.0:1
- Aspiration TA
- Governor Type Woodward
- Fuel System Mechanical unit injection
- Bore 170 mm6.69 in
- Displacement 69 l4210.64 in³
- Stroke 190 mm7.48 in
- Industry power-generation-diesel-hfo
EQUIPMENT
3516 (50 Hz) Standard Equipment
- Air Inlet System
- Air Cleaner; single element canister type
- Control Panels
- EMCP 4.2
- Emergency stop pushbutton
- 24 Volt DC operation
- Environmental sealed front face
- Text alarm / event descriptions
- Generator mounted - rear facing
- Generator set packages include Caterpillar' s Voltage Regulator.
- IVR includes reactive droop capability, 3-phase voltage sensing, KVAR / PF modes, RFI suppression, min /max exciter. Limiter and exciter diode monitor
- Controls: Speed adjust - Auto / start / stop control - Engine cool-down timer - Engine cycle crank - Alarm acknowledge - Lamp test - Load histogram feature - PLC functionality - Customizable screens -0 True RMS AC metering, 3-phase, +/-2% accuracy
- Digital indication for
- RPM - DC volts
- DC volts
- Operating hours
- Oil pressure (psi, kPa or bar)
- Coolant temperature
- Volts (L-L & L-N)
- Frequency (Hz)
- Amps (per phase & average)
- Power Factor (per phase & average)
- kW (per phase, average & percent)
- kVA (per phase, average & percent)
- kVAr (per phase, average & percent)
- kW-hr (total)
- kVAr-hr (total)
- Warning/shutdown with common LED indication of shutdowns for
- Low oil pressure
- High coolant temperature
- Overspeed
- Emergency stop
- Failure to start (overcrank)
- Low coolant temperature
- Low coolant level
- Programmable protective relaying functions:
- Generator phase sequence
- Over / Under voltage (27/59)
- Over / Under frequency (81 o/u
- Reverse Power (kW) (32)
- Reverse Reactive Power (kVAr) (32RV
- Overcurrent (50/51)
- Communications:
- Customer data link (Modbus RTU)
- Accessory module data link
- Serial annunciator module data link
- Cat Connect
- 3 Analog inputs
- 6 Customer programmable digital inputs
- Number of I/O varies on options selected:
- 4 Programmable relay outputs (Form A)
- 1 Programmable relay outputs (Form C)
- 1 Programmable digital outputs
- Cooling System
- Certified standard PGS provided
- ATAAC - 3516E Package Radiators shipped installed
- Exhaust System
- Dry exhaust manifold
- Flanged faced outlet(s)
- Fuel System
- Secondary fuel filters
- Fuel cooler; not included with packages without radiator
- Flexible fuel lines - shipped loose
- Fuel priming pump
- General
- Caterpillar yellow with high gloss black rails and radiator
- Right hand servicing
- Flywheel and flywheel housing - SAE No. 00
- SAE Standard rotation
- Generator and Attachments
- 3 Phase brushless, salient pole
- Six lead
- Low voltage:
- Random wound
- Internal Excitation
- Winding temperature detectors
- NEMA Class H insulation, Class H temperature rise at 40C ambient (125C prime/150C standby)
- Busbar connections, top center mounted, top cable entry
- NEMA standard hole pattern
- Medium Voltage:
- Form wound
- Permanent magnet
- Winding temperature detectors
- NEMA Class H insulation, Class H temperature rise at 40C ambient (125C prime/150C standby)
- NEMA standard hole pattern
- High Voltage:
- Form wound
- Permanent magnet
- Winding temperature detectors
- Anti Condensation Space Heater
- Class H insulation, Class F temperature rise at 40C ambient (105C prime/130C standby)
- Governing System
- ADEM A3
- Literature
- English
- Lubrication System
- Lubricating oil
- Gear type lube oil pump
- Integral lube oil cool
- Oil filter, filler and dipstick
- Oil drain lines and valve
- Fumes disposal
- Mounting System
- Rails - engine / generator / radiator mounting
- Anti-vibration mounts (shipped loose)
- Rubber anti-vibration mounts (shipped loose)
- Starting System
- 24 Volt electric starting motor
- 45 Amp charging alternator
- Battery and battery rack w/cables
- Battery disconnect switch
3516 (50 Hz) Optional Equipment
- Control System
- EMCP 4.3, EMCP 4.4
- Air Inlet System
- Single element filter
- Dual element air cleaner
- Cooling System
- Standard ambient radiators
- Standard ambient ATAAC radiators
- Optional installed radiators
- Optional installed ATAAC radiators
- Water level switch gauges
- Coolant
- Crankcase System
- No explosion relief valves
- Explosion relief valves
- Ventilation system
- Exhaust System
- Elbows
- Flange and exhaust expanders
- Flanges
- Flexible fittings
- Y-Adapters
- Mufflers
- Exhaust offset
- Tier 4 clean emissions module
- Tier 4 dosing cabinet
- Tier 4 clean emission MOD Kits
- Clean emission parts
- Fuel System
- Primary fuel filter
- Fuel Priming Pumps (Tier 4) - Manual or electric
- General
- US aid emblem
- Special paint (Colors other than Caterpillar yellow or high performance paints)
- Generators and Attachments
- Low / medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
- Low / medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, PM, No. of Leads = 6, Pitch = .6667: 1600 and 1800 Frames
- Space heater
- Generator conversion
- Thermostate for space heater
- Alternator air cleaner
- Differential current transformers (DCT)
- Differntial current transformers (DCT) 8.7 kV and 15 kV classes
- Instrumentation
- Pyrometer and thermocouples
- Lubrication System
- Lube oil in standard sump
- Oil level regulator
- Prelube pumps
- Mounting System
- Puck style low efficiency isolators
- Spring type vibration isolators
- IBC vibration isolators
- Power Connections
- Ground cables between generator and terminal box
- Neutral ground connections
- Center post busbar
- Right side power connections
- Left side power connections
- Rear power connections
- 2700 Frame, four lead, four terminal
- Low voltage circuit breakers
- Special Tests / Reports
- Canadian Standards Association certification
- IBC certification
- OSHPD certification
- PGS test report @ 1.0 power factor
- PGS test report @ 0.8 power factor
- Standard engine test charge
- generator test report
- Fuel consumption test
- Generator set fuel consumption test
- Torsional vibration analysis reports
- Starting and Charging
- Engine barring device
- 24 Volt battery set - Dry
- 10, 20, 35 and 50 amp battery chargers
- Electric starting motors
- Air starting motors
- Starter cover
- Air pressure regulator
- Jacket water heaters
- Extended Service Coverage
- Platinum, Gold and Silver coverage
RELATED PRODUCTS
3412C (50 Hz)
power generation diesel hfo
- Height Maximum: 1906 mm75 in
- Length Maximum: 162.4 mm4135 in
- Width Maximum: 1989 mm78.3 in
3512A (50 Hz)
power generation diesel hfo
- Minimum Rating: 1000 kVA
- Maximum Rating: 1400 kVA
- Voltage: 220 to 13800 Volts
3512B (50 Hz)
power generation diesel hfo
- Height Maximum: 2367 mm93.2 in
- Length Maximum: 5637 mm221.9 in
- Width Maximum: 2286 mm90 in
3516 (50 Hz)
power generation diesel hfo
- Height Maximum: 2367 mm93.2 in
- Length Maximum: 5919 mm232.9 in
- Width Maximum: 2286 mm90 in
3516B (50 Hz)
power generation diesel hfo
- Height Maximum: 2367 mm93.2 in
- Length Maximum: 5928 mm233.4 in
- Width Maximum: 2286 mm90 in
3516B DGB™ (50 Hz)
power generation diesel hfo
- Minimum Rating: 1750 kVA
- Maximum Rating: 2275 kVA
- Voltage: 220 to 11000
3516E (50 Hz)
power generation diesel hfo
- Height Maximum: 3476 mm136.9 in
- Length Maximum: 9195 mm362 in
- Width Maximum: 2552 mm100.5 in
C1.5 (50 Hz)
power generation diesel hfo
- Height Maximum: 1054 mm41.5 in
- Length Maximum: 1400 mm55.1 in
- Width Maximum: 620 mm24.4 in
C2.2 (50 Hz)
power generation diesel hfo
- Height Maximum: 1115 mm43.9 in
- Length Maximum: 1500 mm59.1 in
- Width Maximum: 620 mm24.4 in