KEY SPECS
- Minimum Rating 3000 kVA
- Maximum Rating 3500 kVA
- Voltage 380 to 11000 volts
OVERVIEW
BENEFITS
-
- non current
-
- non current
-
- non current
FEATURES AT A GLANCE
Design Criteria
The generator set accepts 100% rated load in one step per NFPA 110 and meets ISO 8528-5 transient response.
Cat Diesel Engine
Generator
EMCP Control Panel
The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP4 systems can be further customized to meet your needs through programming and expansion modules.
Seismic Certification
Single-Source Supplier
Fully prototype tested with certified torsional vibration analysis available
World Wide Product Support
Cat Dealers provide extensive post sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Cat® SOSSM program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products.
UL 2200 / CSA - Optional
SPECIFICATIONS
- Minimum Rating 3000 kVA
- Maximum Rating 3500 kVA
- Voltage 380 to 11000 volts
- Frequency 50 Hz
- Speed 1808 rpm
- Emissions/Fuel Strategy Tier 2 Equivalent
- Displacement 78.1l
- Engine Model 3516E, V-16, 4-Stroke Water-Cooled Diesel
- Compression Ratio 14.7:1
- Aspiration ATAAC
- Governor Type ADEM� A5
- Fuel System Electronic Unit Injection
- Bore 170mm
- Stroke - HD 215mm
- Width - Maximum 2552mm
- Length - Maximum 9195mm
- Height - Maximum 3476mm