US
METRIC
3412C | 900 kVA
KEY SPECS
- Maximum Rating 680 kVA
- Minimum Rating 680 kVA
- Emissions/Fuel Strategy Low Fuel Consumption
OVERVIEW
BENEFITS
-
Accepts 100% block load in 1 step
- Can handle large loads without affecting operations
-
Utilizes the latest ADEM 5 Controllers
- Provides precise control over entire range of loads
-
Upgradeable controls. Allows for easy retrofit of EMCP 4.3/4.4 Controllers
FEATURES AT A GLANCE
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
SR500 Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
EMCP 4 Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 50°C (122°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
- EU Declaration of Conformity
- EU Declaration of Incorporation
- Eurasian Conformity (EAC)
One Safe Source
- Components used in the generator set are selected based on seamless design integration to provide the optimum performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
World Wide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
SPECIFICATIONS
- Maximum Rating 680 kVA
- Minimum Rating 680 kVA
- Emissions/Fuel Strategy Low Fuel Consumption
- Voltage 380 to 415 Volts
- Frequency 50 Hz
- Speed 1500 rpm
- Duty Cycle Standby, Prime
- Engine Model 3412C TA, V-12, 4-Stroke Water-Cooled Diesel
- Bore 137.2mm
- Stroke 152.4mm
- Displacement 27.02l
- Compression Ratio 13:01
- Aspiration Turbocharged, Air to Air Aftercooled
- Fuel System Pump and Lines
- Governor Type ADEM™ A5
- Length - Maximum 4125mm
- Width - Minimum 1906mm
- Width - Maximum 1989mm
- Height - Maximum 1906mm
- Dry Weight - Genset (minimum) 5461kg
- Dry Weight - Genset (maximum) 5910kg